LAMILUX SMOKE EXTRACTION FROM STAIRCASES
THE LAMILUX STAIRCASE SET OFFERS SMOKE EXTRACTION FROM STAIRCASES IN ACCORDANCE WITH GERMAN BUILDING REGULATIONS
A geometric smoke removal surface of 1 m² – or at least 5% of the floor area of the staircase – is required to achieve smoke removal from staircases in accordance with German Building Regulations. The CI System Rooflight Dome F100, Glass Element F100 and Glass Element FE/FP/FW can therefore be equipped with the LAMILUX Staircase Set for automatic opening. We recommend 120cm x 120cm and 100cm x 150cm as optimum skylight dimensions.
ADVANTAGES
LAMILUX SMOKE EXTRACTION FROM STAIRCASES
- The skylight dimensions of 120cm x 120cm produce a geometrically unrestricted opening area of 1.02 m² and 1.07 m² for 100cm x 150cm
- Network-independent
- Electrically controlled with ventilation system
- Assembly kit ready for installation with all required motors, assembly instructions and connection plans
- Easily fitted by an electrician
- Compatible with CI System Rooflight Dome F100 and the Flat Roof Windows: CI System Glass Element F100, CI System Glass Element F, CI System Glass Element FP / FW
Motor line - cable cross-sections | |||
---|---|---|---|
Number of motors | 1 | 2 | |
Max. cable length | 3 x 1,5 mm² | 100 | 50 |
In metres | 3 x 2,5 mm² | 170 | 85 |
(Cross section: x2) | 5 x 2,5 mm² | 300 | 150 |
STANDARD COMPONENTS
LAMILUX SMOKE EXTRACTION FROM STAIRCASES
- Electric motor, 500mm stroke, 24V, with integrated load disconnection
- Control unit for a maximum of two motors with control connectors for SHEV buttons, ventilation buttons and various peripherals such as smoke detectors*, thermal detectors* or wind and/or rain sensors* (*available as an option)
- Two SHEV buttons with visual display, surface-mounted (quantity in accordance with customer requirements)
- Flush-mounted ventilation button